Business Type: Manufacturer
Main Products:Generator Microprocessor-based Protection DeviceMicrocomputer Monitoring SystemDiagitalized Microprocessor-based Protection Devicemicroprocessor governorMicroprocessor Excitation PanelLow Voltage SwitchgearsLow Voltage Power Distribution CubicleHV/LV Pre-assembled Substation
ID:20102827240
Category: Electrical & Power Energy Electrical Controls
MOQ:1.00 Piece(s)
Low VoltagSwitchgearsDrawableCustomizable
T/T
1. Structural features
l The series products use the structural section combination as the basic framework. All structural components are fixed with screws. After forming the basic framework, the doors, baffle, clapboard, drawer, mounting bracket, busbar and electrical components are fixed as required to make up the complete switchgear. The product has below features:
l The framework uses rolled section. Positioned by three-dimensional board, and connected by bolt, without welding structure, in order to avoid welding deformation and stress and improve the installation accuracy.
l The installation hole of frame and accessories are changed based on module quantity E=20mm。
l All internal structure are galvanized, the external structure are sprayed with static epoxy powder after pickling and phosphating treated.
l In inlet cabinet of power control center (PC), the top is the horizontal bus, the lower part of horizontal bus is the circuit breaker room, the domestic intelligence circuit breaker can be chosen for indoor use, it can also equipped with circuit breaker of foreign brands according to the requirement of the user, such as ABB, Schneider's products.
2. Ambient conditions
l Ambient air temperature ≤+40℃ and no less than -5℃, the average temperature within 24h ≤+35℃;
l For indoor use, the elevation of using site ≤ 2000m (above this can be negotiated)
l The relative humidity should not exceed 50% at +40℃, while at lower temperatures, larger relative humidity is acceptable, e.g. 90% at +20℃. Considering the change of temperature may sometime cause the condensation, the daily average should be less than 95% and the monthly average less than 90%;
l The gradient between installation surface and vertical plane is ≤ 5°;
l The device should be installed in the location without violent vibration and impact to prevent the electrical components from corrosion.
l For special requirements, please contact the manufacturer for solution.
3. Technical parameters
No. | Item | Unit | Parameters | |
1 | Rated operating frequency | Hz | 50-60 | |
2 | Rated operating voltage | V | AC:380(660) 10/0.4 0.4 | |
3 | Rated insulation voltage | V | 660 2000 | |
4 | Rated operating current | Horizontal busbar | A | 1600-3150 16-65 |
Vertical busbar | A | 400-800 | ||
5 | Rated peak withstand current | Horizontal busbar | KA | 80(Effective value)/1S |
Vertical busbar | KA | 50(Effective value)/1S | ||
6 | Ligntning impulse withstand voltage | Horizontal busbar | KA | 175 |
Vertical busbar | KA | 110 | ||
7 | Main circuit connector | A | 200、400、600 | |
8 | Auxiliary circuit connector | A | 16 | |
9 | Power frequency withstand voltage | V/min | 2500 | |
10 | Max capacity of control motor | KW | 0.45-155 | |
11 | Protection grade | IP40 IP23 IP30 | ||
12 | Operation mode | Local/Remote/Auto IP23 IP30 | ||
4. Size specification
No | Description | Rated current (A) | Power inlet/ outlet method | Configuration function | External dimension (mm) | Height of drawer (mm) | Qty of drawer (mm) |
1 | Smart CB | 630A | Busbar inlet from top/cable inlet from bottom | Power/ Bus couple | 800*800*2200 | 1200 | 6*200 |
2 | Smart CB | 800A | Busbar inlet from top/cable inlet from bottom | Power/ Bus couple | 800*800*2200 | 1200 | 6*200 |
3 | Smart CB | 1250A | Busbar inlet from top/cable inlet from bottom | Power/ Bus couple | 800*800*2200 | 1200 | 6*200 |
4 | Smart CB | 1600A | Busbar inlet from top/cable inlet from bottom | Power/ Bus couple | 800*800*2200 | 1200 | 6*200 |
5 | Smart CB | 2000A | Busbar inlet from top/cable inlet from bottom | Power/ Bus couple | 800*800*2200 | 1200 | 6*200 |
6 | Smart CB | 2500A | Busbar inlet from top/cable inlet from bottom | Power/ Bus couple | 1000*800*2200 | 1200 | 6*200 |
7 | Smart CB | 3150A | Busbar inlet from top/cable inlet from bottom | Power/ Bus couple | 1000*800*2200 | 1200 | 6*200 |
8 | Smart CB | 630A | Busbar inlet from top/cable inlet from bottom | Dual power switch | 800*800*2200 | 1200 | 6*200 |
9 | Smart CB | 800A | Busbar inlet from top/cable inlet from bottom | Dual power switch | 800*800*2200 | 1200 | 6*200 |
10 | Smart CB | 1250A | Busbar inlet from top/cable inlet from bottom | Dual power switch | 800*800*2200 | 1200 | 6*200 |
11 | Smart CB | 1600A | Busbar inlet from top/cable inlet from bottom | Dual power switch | 800*800*2200 | 1200 | 6*200 |
12 | Smart CB | 2000A | Busbar inlet from top/cable inlet from bottom | Dual power switch | 800*800*2200 | 1200 | 6*200 |
13 | Smart CB | 2500A | Busbar inlet from top/cable inlet from bottom | Dual power switch | 1000*800*2200 | 1200 | 6*200 |
14 | Smart CB | 3150A | Busbar inlet from top/cable inlet from bottom | Dual power switch | 1000*800*2200 | 1200 | 6*200 |
15 | MCCB | 32-100 | Inlet from left/ Onlet from right | Feeder outlet | 600*800*2200 | 200 | 1*200 |
16 | MCCB | 125-225 | Inlet from left/ Onlet from right | Feeder outlet | 600*800*2200 | 200 | 1*200 |
17 | MCCB | 225-400 | Inlet from left/ Onlet from right | Feeder outlet | 600*800*2200 | 400 | 2*200 |
18 | MCCB | 400-630 | Inlet from left/ Onlet from right | Feeder outlet | 600*800*2200 | 400 | 2*200 |

Business Type:Manufacturer