Business Type: Manufacturer
Main Products:gatewayIO moduleindustrial switchprotocol gatewayremote IODistributed IO
ID:20110330732
Category: Manufacturing & Processing Machinery General Industrial Equipment
MOQ:1.00 Piece(s)
Io/Moudle Network Profibus-DpdapterIo Moudle
T/TWestern UnionPaypalOthers
Product Overview
Remote IO system consists of network adapter module and extended IO module.
The network adapter module controls fieldbus communication and it realizes
communication link with host station controller or host computer software.
The extended IO module controls the connection with the input and output
sensors in the field. At first the Input IO module collects the field signals and sends it
to the network adapter through the internal bus. Secondly the controller reads and
processing data from the adapter through the field bus, and it writes the output data
into the network adapter, then the network adapter could write the output data into the
output IO module via the internal bus, so the the field equipment control could be
realized.
According to the communication interface of the controller system, the network
adapter could select the corresponding bus module and mainstream industrial
communication protocols including Modbus, Profibus-DP, Profinet, EtherCAT,
EtherNet/IP, CANsopen, CC-Link, PowerLink, etc. And there are 6 categories of
extended IO modules such as: digital input module, digital output module, analog
input module, analog output module, special module, hybrid IO module, etc.
The network adapter and the extended IO module could be freely combined
according to the field requirements, and it could achieve lower cost with the RemoteCN-8012 Profibus-DP Network Adapter
1 Module Overview
CN-8012 PROFIBUS-DP network adapter supports access of standard
PROFIBUS-DP, and the protocol version it supports is DPV0.
2 Technical Parameter
Adapter Hardware Parameter
System Power
Nominal:24Vdc, Range: 9-36Vdc
Reverse Protection: YES
Power Consumption 30mA@24Vdc
Internal Bus Supply
Current
Max:2.5A@5VDC
Isolation System Power to Field Power Isolation
Power Supply Nominal:24Vdc, Range:22-28Vdc
Field Power Current Max. DC 8A
IO Modules Supported 32 pcs
Wiring Max.1.5mm2(AWG 16)
Mounting Type 35mm DIN-Rail
Size 115*51.5*75mm
Weight 130g
Environment Specification
Operation Temperature -40~85oC
Operation Humidity 5%-95%( No Condensation)
Protection Class IP20
Profibus-DP Parameter
Protocol PROFIBUS DPV0
Interface Type DB9 female head
Station Type PROFIBUS Slave
Station Address Dial code switch configuration
Topology Bus topology
Configuration Max.
Length
232 bytes
IO data Max.
Length
Input: Max. 244 bytes, Output: Max. 244 bytes,
Sum of input and out put: Max. 288 bytes

Business Type:Manufacturer
Online Supplier